China CSC-241C Digital Plant Auxiliary Transformer Protection and Control Device - China Supplier China CSC-241C Digital Plant Auxiliary Transformer Protection and Control Device - China Supplier China CSC-241C Digital Plant Auxiliary Transformer Protection and Control Device - China Supplier China CSC-241C Digital Plant Auxiliary Transformer Protection and Control Device - China Supplier China CSC-241C Digital Plant Auxiliary Transformer Protection and Control Device - China Supplier

CSC-241C Digital Plant Auxiliary Transformer Protection and Control Device

Price:666
Industry Category: Instruments & Meters/Special Instruments/Chemical Instruments
Product Category:
Brand: 北京四方
Spec: CSC-241C


Contact Info
  • Add:宜昌市西陵區(qū)港城路6號, Zip: 443100
  • Contact: 蔣應(yīng)娟
  • Tel:18062398092
  • Email:3052844599@qq.com

Other Products

Description
Additional Information

Beijing Sifang CSC-241C Digital Plant/Station Transformer Protection and Control Device
1.1 Device Introduction

This device is suitable for the protection and control of station or plant transformers and can be installed locally in switchgear.
1.1.1 Protection Functions
a) Instantaneous overcurrent protection for phase-to-phase faults;
b) Overcurrent protection;
c) Overload alarm or trip function;
d) Current acceleration protection;
e) Zero-sequence current protection, operable in definite-time or inverse-time mode;
f) Undervoltage protection with current blocking;
g) Non-electrical protection;
h) F-C overcurrent blocking function.
1.1.2 Control and Monitoring Functions
a) 15-channel digital input for telemetry acquisition, device status change telemetry, and fault telemetry;
b) Remote opening and closing of normal circuit breakers;
c) Telemetry of analog quantities such as Ua, Ub, Uc, Ia, Ib, Ic, P, Q, cos?;
d) Various event SOEs, etc.;
e) 2-channel pulse P and Q inputs.
1.1.3 Other Functions
a) PT broken wire alarm;
b) Control circuit broken wire alarm;
c) Spring not charged alarm;
d) Fault recording;
e) 32 setting groups;
f) 4-20mA output.
2.2 Protection Elements
2.2.1 Overcurrent Element
Overcurrent protection current and time settings can be independently set. The starting condition is:
MAX(IΦ)> MIN(Id ); where Id is the overcurrent setting, IΦ is the phase current.
The operation conditions are:
a) IΦ>Idz; where Idz is the current setting, IΦ is the phase current;

b) is the time delay setting.
Overcurrent protection is enabled or disabled via a software setting. When tripping, it also trips the four branches of the transformer via four backup outputs. When backplane terminals X5.6
and X5.7 are used as general telemetry, a combined software-hardware setting mode can be selected, where X5.6 is the hard contact input for instantaneous overcurrent protection, and X5.7 is the
hard contact input for overcurrent protection.

2.2.2 Overload Protection
The overload element monitors the three-phase load current. If the maximum phase current exceeds the setting and the duration exceeds the time delay setting, an alarm signal is issued or the load is shed based on the control word setting. KG1.0=0: overload issues an alarm signal; KG1.0=1: overload trips and issues an alarm signal.
The operation conditions are:
a) MAX(IΦ)>Ifh, where Ifh is the overload current setting;
b) T> time setting.
The overload function is enabled or disabled via a software setting, and the control word selects whether overload acts on trip or alarm. When tripping, it also trips the four branches of the transformer via four backup outputs.

2.2.3 Current Acceleration Protection
When the transformer is manually or automatically energized into a permanent fault, if any phase current exceeds the current acceleration setting, after the current acceleration time delay setting, the device trips and also trips the four branches of the transformer via four backup outputs.
The operation conditions are:
a) IΦ>Idz; where Idz is the current setting, IΦ is the phase current;
b) Pre-closing state (circuit breaker open for 10 seconds);
c) Circuit breaker closed;
d) T>Tjs; where Tjs is the acceleration protection time delay setting.

Industry Category Instruments & Meters/Special Instruments/Chemical Instruments
Product Category
Brand: 北京四方
Spec: CSC-241C
Stock: 500
Manufacturer:
Origin: China / Jiangsu / Nanjingshi
About Toocle.com - Partner Programme - Old Version
Copyright ? Toocle.com. All Rights Reserved.
(浙)-經(jīng)營性-2023-0192
ChatGlobal Chat Now 禹城市| 房产| 乌拉特中旗| 温泉县| 托克逊县| 乌什县| 新津县| 高雄市| 丽水市| 县级市| 东乌| 霍林郭勒市| 原平市| 广东省| 陇西县| 凌源市| 儋州市| 宁都县| 信丰县| 赤城县| 苏尼特左旗| 安塞县| 望都县| 明光市| 余姚市| 奈曼旗| 黎川县| 孝昌县| 城步| 綦江县| 江口县| 峡江县| 贵南县| 平昌县| 江源县| 稷山县| 汉中市| 河池市| 正镶白旗| 丰镇市| 洪洞县|